Water Ledger Methods

Methods, all states › Cooling systems

Data Center Cooling

How heat moves from the computers to the outdoors, the four heat rejection designs the calculator compares, the three cooling plant setups it offers inside the building, the twelve combinations of the two, and how a plant runs through the year. The calculator's water and electricity follow from these choices. Model version 1.17. Every state uses the same model.

The heat path · Heat rejection designs · Three plant setups · Twelve combinations · Through the year · Water against power · What is uncertain · References

The heat path

Computers turn nearly all the electricity they use into heat. So do the power supplies, lights and fans around them. The cooling system moves that heat out of the building, in steps, from the chips to the outdoor air.

Section through a data center, showing its coolingA cut through a data center building. On the left, air handlers cool hot air over water coils and fans blow it into the data hall. In the hall, racks of computers draw cool air from the cold aisles and exhaust warm air into enclosed hot aisles, which rise to the space above the ceiling and return to the air handlers. A liquid-cooled rack sends coolant to a coolant distribution unit. Facility water pipes carry the heat to the plant room, where pumps, a plate heat exchanger and a chiller pass it to an outdoor loop. Glycol rises to dry coolers on the roof, which release the heat as warm air. As the alternative, dashed pipes lead to a cooling tower in the yard, which evaporates part of its water; make-up water comes from the utility main through a meter and blowdown goes to the sewer.SECTION THROUGH A DATA CENTERCooling, schematic. Not to scale.CDUwater vaporMfacility waterreturn airoutdoorloopor, towers:water mainto sewerROOFCOLD AISLEHOTHOTAIR HANDLERSDATA HALLPLANT ROOMYARD123456789101112

Scroll sideways to see the whole building.

  1. Racks of computers. Server fans pull cool air from the cold aisle through the computers and push it out the back, about 12 K warmer.
  2. Hot aisle. Walls and a roof between the backs of two rows keep the hot air apart; it rises into the space above the ceiling and goes back to the air handlers.
  3. Air handlers. The hot air passes over coils carrying facility water, and a wall of fans blows it, cooled, back into the hall.
  4. Liquid-cooled rack. Cold plates on the chips carry a coolant through manifolds at the back of the rack. Part of the heat still leaves by air.
  5. Coolant distribution unit (CDU). A heat exchanger and pump pass the racks' heat to the facility water.
  6. Facility water. Two pipes run the length of the building: warm water to the plant, cool water back.
  7. Pumps move the facility water around its loop.
  8. Plate heat exchanger. In cool weather the outdoor loop cools the facility water through it, with no compressor (the economizer). It also keeps the outdoor loop's water apart.
  9. Chiller. In warm weather its compressor moves heat from the facility water (lower barrel) to the outdoor loop (upper barrel), which can then run hotter than the outdoors.
  10. Dry coolers on the roof. Fans pull outdoor air across V-shaped coils carrying glycol, so the heat leaves as warm air. Hybrid units add a wet section and adiabatic units add wet pads, used in hot weather.
  11. Cooling towers, the other way to shed the heat. Warm water sprays over fill, outdoor air rises through it, and part of the water evaporates and leaves as vapor.
  12. Make-up water and blowdown. The utility's main replaces what evaporates, and blowdown drains to the sewer to keep minerals from building up. Here, through the meter, is where cooling shows up in a campus's water use.
Figure 1. A section through a data center, with the cooling drawn as if the walls were glass. Air spaces are tinted warm or cool. A campus sheds its heat with dry coolers, towers or a hybrid of the two; both are drawn here, the towers dashed. Schematic: the parts are real, the proportions are not.
The heat path from the computers to the outdoorsAir-cooled computers send hot air to air handler coils; liquid-cooled computers send warm coolant to coolant distribution units, and some of their heat by air to the air handlers. Both pass the heat to the facility water loop, which carries it to the cooling plant: an economizer when outside air is cool enough, chillers when it is not. A plate heat exchanger passes the heat to the outdoor loop: glycol to dry coolers, which release it as warm air, or open water to cooling towers, which release it as warm air and water vapor.DATA HALLAir-cooled computersserver fans move the airLiquid-cooled computerscold plates on the chipshot aircoolantpart by airAir handler coilshot air in, supply air outCoolant units (CDUs)coolant to facility waterFacility water looppumped to the plant warm, back coolPLANTEconomizerfree cooling: no compressorChillerselectricity, in warm hoursPlate heat exchangerkeeps the outdoor loop apartglycol loopopen waterOUTDOORSDry coolerswet pads in assistCooling towersevaporate part of itwarm airwarm air, water vapor143568981011
Figure 2. The same heat path as a diagram, numbered as in Figure 1. Nearly all the electricity becomes heat, which moves from the computers to the facility water and from there to the outdoors. Liquid-cooled computers still put part of their heat into the room's air. Dry coolers run a glycol loop so they do not freeze; a hybrid has both a dry and a wet section; air-cooled chillers reject their heat through their own coils. Diagram, not to scale.

Air-cooled computers

Fans in each server pull air from the cold aisle and push it, warmer, into the hot aisle. Air handlers (computer room air handlers, or CRAHs, and fan walls) pass the hot air over coils carrying facility water and return it to the cold aisle as supply air. ASHRAE recommends supply air no warmer than 27 °C1. Documented designs run 27.8 °C (Schneider)4, 30 °C (OCP's study case)2 and 18.3–29.4 °C (Meta's reference band)3; older chilled-water designs run 18–19 °C15. The air warms about 12 K across the servers in the OCP and Meta cases2,3. The coil's water runs a few degrees below the supply air: 5.0 K in Schneider's design and 6 K in OCP's2,4.

Liquid-cooled computers

Cold plates sit on the processors and carry a coolant through the rack. That coolant loop is the technology cooling system. A coolant distribution unit (CDU) passes its heat to the facility water through a heat exchanger, so the facility water runs a few degrees colder than the coolant: 4–8 K for large units in OCP's paper, 2.8 K in Schneider's design2,4. NVIDIA's 45 °C for its Vera Rubin racks is the coolant at the rack inlet9, not the facility water2. Part of a liquid-cooled rack's heat still leaves by air: 13% in Schneider's racks and 20% in OCP's case2,4. The calculator samples 10–30% [A].

Facility water and chillers

Pumps carry the facility water from the air handler coils and coolant units to the cooling plant and back. It warms 10 K on each pass in Schneider's and OCP's designs2,4; the calculator samples 5–10 K, after Lei and Masanet11. When the outdoors is cool enough, the plant cools the water through heat rejection and a heat exchanger alone, with no compressor: a water-side economizer, or free cooling. When the outdoors is warmer than the water coming back, chillers do all the work, using electricity to move the heat into a hotter loop that the outdoor equipment can shed. In between, the economizer cools the water part of the way and chillers finish it. The calculator follows Lei and Masanet: the economizer's share falls from all to none as the outdoor temperature, plus the equipment's approach, rises from the water's supply temperature to its return temperature11.

Heat rejection outdoors and glycol

Outdoor equipment releases the heat to the air, by evaporating water, by warming the air, or both. This is where the four designs differ. In every design a plate heat exchanger keeps the outdoor loop apart from the facility water. A cooling tower's side is open water. A dry cooler's side is a closed loop of glycol, so it does not freeze in winter. From model 1.10 the calculator takes it as propylene glycol at 30–40% by volume [A], from burst protection to freeze protection for a Great Lakes winter: Dow gives freezing points of -12.7 °C at 30% and -21.1 °C at 40%19. At 20 °C its heat capacity is 3.870 and 3.701 kJ/kg/K, against water's 4.19, and its density 1,025.2 and 1,036.9 kg/m³19. Carrying the same heat takes about 8–13% more flow by mass (our arithmetic), so the glycol pumps use a little more electricity. Glycol is also thicker than water, which would add pump pressure; that is not modeled [A]. It does not change the water a campus uses.

The four heat rejection designs

The calculator compares four designs. They differ in when they evaporate water. The water parts and their sources are on the Michigan methods page, which applies in every state.

"Closed loop" is not one of them. Every design has a closed loop of water inside the building, the plant below. The words say how water moves indoors, not how heat leaves: campuses that say closed loop have dry coolers, pads on the hottest days or cooling towers outside. A rule or a claim that says closed loop leaves the water open until it names the design outside. On the trackers, a proposal that says closed loop and names no dry equipment, and doesn't say it uses no water for cooling, starts with pads on hot days.

Hybrid and pads go wet above the operator's switch setting. Microsoft and Meta state 85-86 °F (29-30 °C); from model 1.16 the calculator samples 26.5-32 °C, the settings that operators' stated time on water implies at their sites. Below it, chillers do the work.

Cooling towersWater sprays over fill and part of it evaporates, all year.
HybridA dry coil most of the year; an evaporative section in warm weather.
Dry with evaporative pads on hot daysA dry coil; wet pads cool the air ahead of it on the hottest days.
DryDry coolers or air-cooled chillers, with chillers on hot days. No water evaporates for cooling.
Figure 3. The four heat rejection designs the calculator compares. Blue marks where water is used. Sketches, not equipment drawings.
DesignWhen it evaporatesWater it uses for coolingElectricity
Cooling towersAll year.Evaporation; drift (droplets carried off in the air); blowdown (water drained to keep minerals from building up). Blowdown and drift together are evaporation divided by cycles of concentration less one.Tower fans slow in cool weather; water-cooled chillers in warm hours. The lowest power of the four.
HybridFrom a switch point up, fully evaporative at the location's 0.4% design dry-bulb [A].Evaporation, drift and blowdown in warm hours only.Dry cooler fans and glycol pumps most of the year; chillers trim the water when the dry coil cannot hold it.
Dry with evaporative pads on hot daysAbove the switch point.Water evaporated from pads ahead of the coil, plus a bleed of 0–50% of it, by pad type.As hybrid; the pads extend the hours a dry coil can hold the water.
DryNever.No water evaporates for cooling. The building's loop is filled once and topped up for small leaks.Air-cooled chillers carry what the dry coolers cannot, so the most power in hot hours.

Every design also takes water that is not for cooling: staff water, maintenance and cleaning, loop top-ups, and humidifiers in very dry air. Coils that dehumidify outside air in humid weather make condensate, which goes out with the wastewater. Electricity is reported as power and as PUE, facility power over the computers' power. The switch point for hybrid and assist is an operator's setting: the outdoor dry-bulb where the dry coil can no longer hold the loop's water, give or take 2 K, within the settings makers publish [A].

Three cooling plant setups

Inside the building, the plant can run the air handlers and the liquid-cooled racks on one facility water loop, give the liquid-cooled racks a warmer loop of their own, or cool everything with chilled water. The calculator offers all three from model 1.10. One shared loop is the default.

One shared facility water loop (default)

Air handlerssupply air 24–30 °CCoolant unitsliquid 0–100%one loopabout 16–28.5 °CCooling planteconomizer, chillers, heat rejection

Liquid-cooled racks take the air loop's water. An air-cooled hall is this plant with few liquid racks. Documented by OCP, Vertiv and Uptime2,5,6,7.

A separate warm-water loop

Air handlerssupply air 24–30 °CCoolant unitsliquid 70–100% [A]cool loopabout 16–28.5 °Cwarm loop30–42 °C [A]Cool-loop planteconomizer, chillersWarm-loop plantmostly free cooling

A purpose-built liquid-cooled hall, with the air hall on its own cooler loop. Documented by Schneider4.

A conventional chilled-water plant

Air handlerssupply air 18–22 °CCoolant unitsliquid 0–20% [A]chilled water7–13 °CChillerseconomizer in cold weather

The older plant, common in colocation buildings. Documented in ASHRAE 90.4's worked example14,15.

Figure 4. The three cooling plant setups the calculator offers (model 1.10). Temperatures are facility water supply; the shared loop's range follows from the supply air through the air handler coil, and the chilled water is set. Diagram, not to scale.

One shared facility water loop (default)

One loop serves both the air handlers and the coolant units, so the liquid-cooled racks get the air loop's water. This is the common documented practice today. OCP's 2024 study case runs one loop at 24/34 °C feeding coolant units and air units, with 30 °C supply air (Fig. 10)2. Vertiv's GB200 reference designs #006 and #007 serve the coolant units and the perimeter air units from one set of chillers5,6. Uptime reports that operators commonly run 18–24 °C water at the coolant units because one loop also carries the air loads7.

A separate warm-water loop

Purpose-built liquid-cooled halls can give the coolant units their own warm loop on dry coolers, with the air hall on a cooler loop. Schneider's Reference Design 109 runs fluid coolers at 37.2/47.2 °C, with adiabatic assist above 32 °C, for the coolant units, and a separate 22.8/32.8 °C chilled water loop for 27.8 °C supply air4.

A conventional chilled-water plant

Older buildings and many colocation buildings cool the air with chilled water from chillers, with an economizer in cold weather. ASHRAE 90.4's worked example for climate zone 5A, the zone of West Michigan's Kent County, supplies 18–19 °C air on 44/56 °F (6.7/13.3 °C) chilled water from one air-cooled chiller15.

Changes to the calculator

Before model 1.10, every campus ran supply air at 27–35 °C, the upper float bound in Lei and Masanet's Table 311, and liquid-cooled computers on a loop of their own at 32–45 °C, two of ASHRAE's W classes. The W classes (W17 to W45) are ceilings: each class runs from 2 °C up to its number, and equipment must perform fully anywhere in that range1. They are not operating points. LBNL's 2024 report assumes W45 for liquid-cooled AI12, and 45 °C facility water is warmer than any reference design we read. So every campus was a warm-water best case.

Effect of the plant

Warmer water lets dry coolers carry the whole load for more hours (Figure 5). So hybrid and assist evaporate less, and dry needs less chiller power. Colder water does the opposite, so the chilled-water plant takes the most electricity of the three. Towers barely change with the plant, because they evaporate all year at any water temperature. In West Michigan, per 100 MW of IT capacity, model 1.17 gives hybrid an average day of about 9,000 gallons on one shared loop, 8,000 on a warm loop and 10,000 with chilled water. Dry draws about +2.2 MW more than towers on average on a shared loop and +1.6 MW on a warm loop; on the peak day, +4.8 and +4.6 MW. Chilled water adds about 5 MW to towers' average against the shared loop. The section below, water against power, sets these side by side.

DesignPlantWater, average day (MGD)Water, peak day (MGD)Power, average (MW)Power, peak day (MW)Power, hottest hour (MW)PUE
Cooling towersOne shared loop0.660.9574.288.9125.61.134
Separate warm loop0.650.8972.483.2117.21.113
Chilled water0.711.0079.595.1134.11.217
HybridOne shared loop0.0090.5076.492.2130.41.174
Separate warm loop0.0080.4674.085.2122.51.132
Chilled water0.010.5482.699.6141.31.274
Dry with evaporative pads on hot daysOne shared loop0.0070.2776.492.7130.91.174
Separate warm loop0.0060.2574.086.1123.21.132
Chilled water0.0070.2982.7100.3142.01.274
DryOne shared loop<0.01<0.0176.493.7133.91.175
Separate warm loop<0.01<0.0174.087.8128.81.133
Chilled water<0.01<0.0182.7101.7145.41.275

Model 1.17's results, not measurements: the ERA5 cell at 42.75° N, 85.50° W (Gaines Township's, in West Michigan), per 100 MW of IT capacity, median of 400 runs, hourly weather 1995–2024 corrected toward nearby stations. Cooling and loop water only, without staff water; the peak day is the 1-in-10-year peak day, at average load; the hottest hour is every computer at capacity in the 1-in-10-year hottest hour.

Twelve combinations

The plant inside and the heat rejection outside are separate choices: three plants and four designs make twelve combinations. All twelve exist, and the calculator computes all of them. Some are much more common than others. In the table, common, real and uncommon are our judgment from the designs cited, not survey data. Where we found no design document for a cell, it says so.

Plant inside \ outsideCooling towersHybridDry with evaporative pads on hot daysDry
One shared loop (default)CommonTowers with a water-side economizer are ASHRAE's typical plant for W17–W27 water3.CommonJudgment; no single design document cited.CommonJudgment; no single design document cited.CommonOCP's study case runs air-cooled free-cooling chillers in dry mode only2.
Separate warm loopUncommon but realFrontier at Oak Ridge: 32 °C water, no chillers, counterflow cooling towers17,18. ASHRAE lists towers for W32–W453.RealJudgment; no single design document cited.RealSchneider's RD109: fluid coolers with adiabatic assist above 32 °C4.Natural fitWarm water lets dry coolers carry the load nearly all year (Figure 5). LBNL's liquid-cooled AI archetype uses dry coolers12.
Chilled waterThe classicWater-cooled chillers on towers, with a water-side economizer: ASHRAE's typical plant for W17–W273. The most common older plant (judgment).UncommonHybrid coolers serving the chillers' condensers. Judgment; no design document cited.RealAdiabatic pre-cooling on air-cooled chillers. Judgment; no design document cited.Common in colocationAir-cooled chillers, with or without free-cooling coils: ASHRAE 90.4's zone 5A example uses one air-cooled chiller15; Schneider's chilled water comes from free-cooling chillers4.

The uncommon pairs are uncommon for plain reasons. A warm loop on towers spends water where dry coolers could hold the loop most of the year (Figure 5). A chilled-water plant usually picks towers, which make its chillers efficient, or air-cooled chillers, which use no water; a hybrid cooler on its condensers sits between the two. The detailed calculator marks the uncommon pairs as shown for comparison.

A Year of Operation

A dry cooler can hold the facility water at its supply temperature when the outdoor air is cooler than that temperature by the coil's approach and the heat exchanger's: about 9.75 K at the calculator's centre values [A]. When the outdoors is warmer than that but still cooler than the returning water, the dry cooler does part of the work. Above the return temperature it can do none of it. A tower works the same way against the wet-bulb temperature, which runs lower, so it holds a given temperature in more hours.

0%25%50%75%100%7 °C7 °C: fully 8%, partly 25%, not at all 67% of hours7 °C: fully 8%, partly 25%, not at all 67% of hours7 °C: fully 8%, partly 25%, not at all 67% of hours8%13 °C13 °C: fully 29%, partly 21%, not at all 50% of hours13 °C: fully 29%, partly 21%, not at all 50% of hours13 °C: fully 29%, partly 21%, not at all 50% of hours29%18 °C18 °C: fully 43%, partly 20%, not at all 36% of hours18 °C: fully 43%, partly 20%, not at all 36% of hours18 °C: fully 43%, partly 20%, not at all 36% of hours43%22.8 °C22.8 °C: fully 56%, partly 24%, not at all 20% of hours22.8 °C: fully 56%, partly 24%, not at all 20% of hours22.8 °C: fully 56%, partly 24%, not at all 20% of hours56%24 °C24 °C: fully 59%, partly 25%, not at all 16% of hours24 °C: fully 59%, partly 25%, not at all 16% of hours24 °C: fully 59%, partly 25%, not at all 16% of hours59%27 °C27 °C: fully 69%, partly 23%, not at all 8% of hours27 °C: fully 69%, partly 23%, not at all 8% of hours27 °C: fully 69%, partly 23%, not at all 8% of hours69%30 °C30 °C: fully 79%, partly 18%, not at all 3% of hours30 °C: fully 79%, partly 18%, not at all 3% of hours30 °C: fully 79%, partly 18%, not at all 3% of hours79%32 °C32 °C: fully 86%, partly 13%, not at all 1% of hours32 °C: fully 86%, partly 13%, not at all 1% of hours32 °C: fully 86%, partly 13%, not at all 1% of hours86%34 °C34 °C: fully 91%, partly 9%, not at all <1% of hours34 °C: fully 91%, partly 9%, not at all <1% of hours34 °C: fully 91%, partly 9%, not at all <1% of hours91%37.2 °C37.2 °C: fully 96%, partly 4%, not at all 0% of hours37.2 °C: fully 96%, partly 4%, not at all 0% of hours96%40 °C40 °C: fully 99%, partly 1%, not at all 0% of hours40 °C: fully 99%, partly 1%, not at all 0% of hours99%45 °C45 °C: fully 100%, partly 0%, not at all 0% of hours100%chilled water7–13 °Cshared loopabout 16–28.5 °Cwarm loop30–42 °C [A]0%25%50%75%100%7 °C7 °C: fully 8%, partly 25%, not at all 67% of hours7 °C: fully 8%, partly 25%, not at all 67% of hours7 °C: fully 8%, partly 25%, not at all 67% of hours8%13 °C13 °C: fully 29%, partly 21%, not at all 50% of hours13 °C: fully 29%, partly 21%, not at all 50% of hours13 °C: fully 29%, partly 21%, not at all 50% of hours29%18 °C18 °C: fully 43%, partly 20%, not at all 36% of hours18 °C: fully 43%, partly 20%, not at all 36% of hours18 °C: fully 43%, partly 20%, not at all 36% of hours43%22.8 °C22.8 °C: fully 56%, partly 24%, not at all 20% of hours22.8 °C: fully 56%, partly 24%, not at all 20% of hours22.8 °C: fully 56%, partly 24%, not at all 20% of hours56%24 °C24 °C: fully 59%, partly 25%, not at all 16% of hours24 °C: fully 59%, partly 25%, not at all 16% of hours24 °C: fully 59%, partly 25%, not at all 16% of hours59%27 °C27 °C: fully 69%, partly 23%, not at all 8% of hours27 °C: fully 69%, partly 23%, not at all 8% of hours27 °C: fully 69%, partly 23%, not at all 8% of hours69%30 °C30 °C: fully 79%, partly 18%, not at all 3% of hours30 °C: fully 79%, partly 18%, not at all 3% of hours30 °C: fully 79%, partly 18%, not at all 3% of hours79%32 °C32 °C: fully 86%, partly 13%, not at all 1% of hours32 °C: fully 86%, partly 13%, not at all 1% of hours32 °C: fully 86%, partly 13%, not at all 1% of hours86%34 °C34 °C: fully 91%, partly 9%, not at all <1% of hours34 °C: fully 91%, partly 9%, not at all <1% of hours34 °C: fully 91%, partly 9%, not at all <1% of hours91%37.2 °C37.2 °C: fully 96%, partly 4%, not at all 0% of hours37.2 °C: fully 96%, partly 4%, not at all 0% of hours96%40 °C40 °C: fully 99%, partly 1%, not at all 0% of hours40 °C: fully 99%, partly 1%, not at all 0% of hours99%45 °C45 °C: fully 100%, partly 0%, not at all 0% of hours100%
Figure 5. Share of hours a dry cooler can hold each facility water supply temperature in West Michigan, at the calculator's centre values for the dry cooler and its heat exchanger (7.5 + 2.25 K) [A]. A calculation on the package's West Michigan 2023–24 hourly test weather (17,544 hours), not a published table. Facility water temperature on the vertical axis. The chilled-water plant sits at 7–13 °C, the shared loop at about 16–28.5 °C and the warm loop at 30–42 °C.

In West Michigan a dry cooler holds 24 °C water fully in about 59–67% of hours, 30 °C in 79–87%, and 37 °C in 96–99% (the lower figure at the calculator's centre coil approach, the higher with a 5 K coil). Chilled water at 7–13 °C gets full free cooling in only 8–36% of hours. Above about 37 °C a West Michigan liquid loop would need no evaporation or chillers in these two years. OCP's published shares for its cool climate zone run higher, 80% full free cooling at 24 °C facility water and 95% at 34 °C2, against 59–67% and 91–95% here. OCP does not name its locations, and its chillers have their own free-cooling coils. We have not resolved the difference.

Facility water supplyDry cooler: fully / partly / not (%)With a 5 K coil (%)Tower: fully / partly (%)
7 °C chilled water, low end8 / 25 / 6715 / 25 / 6024 / 26
13 °C chilled water, high end [A]29 / 21 / 5036 / 20 / 4444 / 23
18 °C43 / 20 / 3650 / 22 / 2859 / 30
22.8 °C shared loop, centre56 / 24 / 2063 / 25 / 1278 / 22
24 °C OCP study case59 / 25 / 1667 / 24 / 983 / 17
27 °C69 / 23 / 878 / 18 / 494 / 6
30 °C79 / 18 / 387 / 12 / 199 / 1
32 °C86 / 13 / 192 / 8 / <1100 / <1
34 °C91 / 9 / <195 / 5 / 0100 / 0
37.2 °C Schneider warm loop96 / 4 / 099 / 1 / 0100 / 0
40 °C99 / 1 / 0100 / <1 / 0100 / 0
45 °C ASHRAE W45 ceiling100 / 0 / 0100 / 0 / 0100 / 0

The partly and not-at-all hours are when each design does something else. Dry runs chillers. Hybrid and assist go wet at the switch point, which sits near where full dry cooling ends, and trim with chillers below it. Towers evaporate throughout. On the hottest days, hybrid runs fully evaporative near the location's design dry-bulb, assist's pads run through the afternoon, and dry leans on its chillers. NVIDIA notes that chillers remain important in hot conditions and that operators often run loops colder than they need to, for margin9. That is why the calculator reports a 1-in-10-year peak day as well as an average day, and peak-day power as well as average power.

Water against power

Cooling towers get rid of a data center's heat by evaporating water. Dry coolers do it with fans and outdoor air, and when the air is too warm for that they turn on chillers, compressors that run on electricity. So the water a dry design saves is paid for in electricity. Three numbers describe the trade: the extra electricity over a year, the extra power in the hottest hour, and the water the power plants evaporate to make that extra electricity.

Over a year the difference is small. In West Michigan, a campus with dry cooling on the shared loop uses about 4% more electricity a year than the same campus with towers, about 24 GWh a year per 100 MW of IT capacity. The model gives about 4% in Loudoun County, Virginia, 6% in Dallas and 10% in Phoenix (model 1.17). The chillers run only in warm hours, and the fans and pumps cost about the same in either design. Published figures agree. Google's air-cooled campus at Storey County, Nevada ran at a PUE of 1.16 in 2024 against 1.09 at its evaporative campus at Henderson, about 6% more (our arithmetic)20. LBNL's 2024 simulations give large air-cooled sites 0.03–0.08 more PUE than evaporative ones12, and Microsoft calls the increase from dropping evaporative cooling "nominal"21.

The difference is at the peak. In the hottest hour of a hot summer every chiller runs. A tower's chillers work against the wet-bulb temperature and an air-cooled chiller against the dry-bulb, 10–24 K hotter in that hour, so an air-cooled chiller needs about twice the electricity per unit of heat at 40–46 °C (our arithmetic from ASHRAE 90.1's rating points and curves23,24). Per 100 MW of IT capacity, dry cooling on the shared loop needs about 8.3 MW more than towers in that hour in West Michigan, and up to 14.8 MW in Phoenix. For a 1-gigawatt campus that is about 83 to 148 MW, in an hour when the grid is already stretched. Amazon puts chillers at 25–35% more electricity than evaporative cooling on the hottest days22; for the cooling electricity alone in that hour, the model gives dry 28–51% more than towers across the four places. Pads and hybrids take part of the peak back: 3.0 and 3.5 MW per 100 MW here.

The power plants' water for the extra electricity is small next to the towers' own. In West Michigan it is about 3% of what towers evaporate on site, on MISO's hourly mix of plants25: 0.017 against 0.52 million gallons a day per 100 MW. The model gives about 4% in Loudoun County, 4% in Dallas and 13% near Phoenix. So dry cooling saves nearly all of the water, even counting the power plants. Pads and hybrids at model 1.17 go wet only above the operator's switch setting, so in West Michigan they evaporate little on site over a year (about 5,500 and 6,900 gallons a day per 100 MW) and use about as much electricity as dry cooling. Their extra electricity's water at the power plants, about 16,900 gallons a day, is larger than their own.

What the power plant water counts. It is the water that cools thermoelectric plants (coal, gas, nuclear and the like), from their reports to EIA. Evaporation from hydropower reservoirs is not counted; whether it belongs to the electricity or to a reservoir's other uses is disputed. In Western states, counting it can reverse the comparison. Near Phoenix, dry cooling's extra electricity costs about 34% of the towers' own water at WRI's factor for the Arizona and New Mexico grid region, which counts reservoirs26, and about twice the towers' own at Torcellini et al.'s factor for Arizona, 7.85 gallons per kWh27 (our arithmetic). In Michigan, Virginia and Texas counting reservoirs does not change which design uses less water. Each state's methods page gives its grid regions both ways.

How cold the building keeps its water matters as much as the design. In West Michigan, the same dry campus uses about 9% more electricity a year on a chilled-water plant (7–13 °C water) than on the shared loop, against 3.6% between dry cooling and towers on the shared loop. In Dallas the model gives about 10% against 5%. A warm liquid loop (30–42 °C water) narrows the yearly gap between dry and towers to 1.8% here; on chilled water it is 4.8%.

DesignPlantMore electricity a yearGWh a yearMore power, hottest hour (MW)Power plant water for the extra (MGD)Its own water evaporated (MGD)Towers evaporate (MGD)Extra as a share of towers'
DryOne shared loop (default)3.6%248.30.017<0.0010.523%
Separate warm loop1.8%1111.60.012<0.0010.512%
Chilled water4.8%3311.30.025<0.0010.564%
Dry with evaporative pads on hot daysOne shared loop (default)3.5%235.30.0170.0050.523%
Separate warm loop1.7%116.00.0120.0050.512%
Chilled water4.7%337.90.0240.0060.564%
HybridOne shared loop (default)3.5%234.80.0170.0070.523%
Separate warm loop1.7%115.30.0120.0060.512%
Chilled water4.7%337.20.0240.0070.564%

Model 1.17's results, not measurements, for the ERA5 cell at 42.75° N, 85.50° W (Gaines Township's, in West Michigan), per 100 MW of IT capacity, from the plant table above [D]. More electricity a year is the ratio of year-average PUE, which leaves out how busy the computers are; GWh a year is that share of the towers' average power times 8,766 hours. The hottest hour and the power plant water are differences between the medians of 400 runs. Power plant water is water consumed (evaporated) at the plants, on MISO's average hourly mix, without line losses; "its own" is the cooling and loop water each design evaporates on site, without staff water. The other places are the same model's runs for those places.

Uncertainty

References

Page numbers are PDF pages. Ranges marked [A] are assumptions drawn from these sources.

  1. ASHRAE Technical Committee 9.9. Emergence and Expansion of Liquid Cooling in Mainstream Data Centers. White paper, 2021. PDF pp. 8 (W classes), 14 (H1 class, recommended 18–22 °C), 15 (recommended upper limit 27 °C), 18 and 20 (facility water today and its direction). https://www.ashrae.org/File%20Library/Technical%20Resources/Bookstore/Emergence-and-Expansion-of-Liquid-Cooling-in-Mainstream-Data-Centers_WP.pdf
  2. Open Compute Project. 30℃ Coolant: A Durable Roadmap for the Future. Rev 1.0, October 1, 2024. Pp. 3 and 16 (30 °C as the technology loop's setpoint), 18–19 (W classes refer to facility water; study case), 21 (coolant unit approach 4–8 K, 10 K loop rise, air side), 22 (Fig. 10, one loop for coolant units and air units, air-cooled free-cooling chillers), 24 (Fig. 12, hours by cooling mode and climate zone). https://www.opencompute.org/documents/30-coolant-a-durable-roadmap-for-the-future-rev1-0-pdf
  3. Open Compute Project and Meta. Liquid Cooling: Drivers, timelines and a case for industry convergence on coolant temperatures. Presentation, PDF dated November 1, 2021. Pp. 7 (Meta's reference supply air, 18.3–29.4 °C, 12.2 K air rise), 15–16 (one primary loop for air and liquid), 24 (ASHRAE's 2021 table of typical plants by W class, reproduced), 25 (30 °C proposed as the facility water temperature). https://www.opencompute.org/wp-content/uploads/2026/07/46c790c34e6f3c5444a57c82db2b2d1da422f29e.pdf
  4. Schneider Electric. EcoStruxure Reference Design 109: 7,392 kW, Tier III, ANSI, Chilled Water, Liquid-cooled AI Clusters (NVIDIA GB200). Document RD109DS, Revision 11, March 14, 2026. Pp. 1, 3, 4, 7: fluid coolers with adiabatic assist above 90 °F (32 °C) at 99/117 °F (37.2/47.2 °C) for the coolant units; separate chilled water at 73/91 °F (22.8/32.8 °C) from free-cooling chillers for fan walls at 82 °F (27.8 °C) supply air; 132 kW liquid-cooled racks, 87% of their heat to liquid. Read from a copy hosted by a third party; Schneider's own PDF could not be opened. https://changguoting.github.io/amd-tradeoff-hub/MI4.pdf
  5. Vertiv. Vertiv 360AI High Density Reference Design for AI, AI Reference Design #006: 4x 1.2MW NVIDIA Blackwell DGX SuperPODs. Datasheet, EMEA, 2025. 80% liquid (direct-to-chip), 20% air; one set of chillers serves the liquid cooling loop's coolant units and the perimeter air units. https://www.vertiv.com/48ebb0/globalassets/documents/brochures/vertiv-reference-design-006-ds-en-emea-2025-gr-00099-web.pdf
  6. Vertiv. Vertiv 360AI High Density Reference Design for AI, AI Reference Design #007: 5x 1.2MW NVIDIA Blackwell DGX SuperPODs. Datasheet. 80% liquid, 20% air; the same shared heat rejection loop as #006. https://vertiv.com/49e8a2/globalassets/documents/ai-hub-reference-design/vertiv-360ai-reference-design-007.pdf
  7. Rahkonen, T. AI and cooling: chilled water system topologies (AI and cooling, Part 4). Uptime Intelligence Update 373, Uptime Institute, June 10, 2025. P. 2: operators commonly select coolant unit supply water of 18–24 °C, because one facility water loop serves liquid and air loads. https://intelligence.uptimeinstitute.com/pdf-download/node/152007
  8. Bizo, D. Performance expectations of liquid cooling need a reality check. Uptime Institute Journal, March 20, 2024. Facility water temperatures appear to be converging around 32 °C. https://journal.uptimeinstitute.com/performance-expectations-of-liquid-cooling-need-a-reality-check/
  9. McKenney and Petty. Maximizing AI factory performance per watt with NVIDIA DSX MaxLPS. NVIDIA Technical Blog, August 24, 2026. Vera Rubin NVL72 at a 45 °C liquid inlet; chillers remain important in hot conditions; operators often run the loop colder than needed. https://developer.nvidia.com/blog/maximizing-ai-factory-performance-per-watt-with-nvidia-dsx-maxlps/
  10. Guthrie, S. Inside the world's most powerful AI datacenter. The Official Microsoft Blog, September 18, 2025. Over 90% of the Fairwater site's capacity on closed-loop liquid cooling. https://blogs.microsoft.com/blog/2025/09/18/inside-the-worlds-most-powerful-ai-datacenter/
  11. Lei, N., and Masanet, E. Climate- and technology-specific PUE and WUE predictions for U.S. data centers using a physics-based approach. Research Square preprint, August 3, 2021, of the article in Resources, Conservation and Recycling 182 (2022) 106323. Table 3 (supply air float bounds, air rise, facility water rise 5–10 K, economizer) and section 3.3. https://doi.org/10.21203/rs.3.rs-769999/v1
  12. Shehabi, A., et al. 2024 United States Data Center Energy Usage Report. Lawrence Berkeley National Laboratory, LBNL-2001637, December 2024. Tables 4.2–4.3, pp. 41–43 (cooling archetypes; liquid-cooled AI at W45 on dry coolers), p. 44. https://doi.org/10.71468/P1WC7Q
  13. Water Ledger cooling model, waterledger-models: datacenter/physics.py and cooling.py, model 1.17 (the plants, the glycol, their ranges and sources are in the comments). https://github.com/northlinehydrology/waterledger/blob/main/packages/waterledger-models/src/waterledger_models/datacenter/physics.py
  14. ASHRAE. Addendum g to ANSI/ASHRAE Standard 90.4-2022, Energy Standard for Data Centers. January 31, 2024. PDF p. 6, informative note 4: the maximum mechanical load values assume an 11 K (20 °F) air temperature rise to 29 °C (85 °F) return air. https://www.ashrae.org/file%20library/technical%20resources/standards%20and%20guidelines/standards%20addenda/90_4_2022_g_20240131.pdf
  15. Amistadi, H. Proposed data center cooling: CRAH with air chiller empirical energy calculations for Albany New York (TMY3). ASHRAE supplemental file to Standard 90.4, September 3, 2020. PDF pp. 6–7: air handlers supplying 64–67 °F (18–19 °C) air on chilled water at 44/56 °F (6.7/13.3 °C) from one air-cooled chiller, ASHRAE climate zone 5A. https://www.ashrae.org/file%20library/technical%20resources/bookstore/supplemental%20files/data-center-with-crah-and-air-chiller-in-5a.pdf
  16. Uptime Institute. Uptime Institute 2024 Cooling Systems Survey: Direct Liquid Cooling Results. Data Report 139, May 2024. P. 1: 22% of respondents use direct liquid cooling; nearly half of them on under 10% of their IT racks. https://intelligence.uptimeinstitute.com/resource/uptime-institute-cooling-systems-survey-2024-direct-liquid-cooling
  17. Kumar, V., Greenwood, S., Brewer, W., Grant, D., Parkison, N., and Williams, W. Thermo-Fluid Modeling Framework for Supercomputer Digital Twins: Part 1, Demonstration at Exascale. Oak Ridge National Laboratory, OSTI ID 2480044. Frontier's high-temperature water loop, economizer heat exchangers and counterflow cooling towers with blowdown. https://www.osti.gov/servlets/purl/2480044
  18. McDowell, R. Stunning Specs: What's inside the Nation's First Exascale Supercomputer Facility? Oak Ridge Leadership Computing Facility, September 29, 2021. A 90 °F (32 °C) cooling water system with no water chillers. https://www.olcf.ornl.gov/2021/09/29/stunning-specs-whats-inside-the-nations-first-exascale-supercomputer-facility/
  19. Dow. DOWFROST Heat Transfer Fluid. Technical Data Sheet, Form No. 180-01314-1019 (October 2019). Pp. 1–3: freezing points (-12.7 °C at 30% and -21.1 °C at 40% propylene glycol by weight, about the same by volume) and heat capacity and density by volume concentration and temperature. Read from a copy hosted by a distributor. https://cdn.shopify.com/s/files/1/0299/3356/8138/files/DOWFROST_Inhibited_Food_Grade_Propylene_Glycol_Heat_Transfer_Fluid_Technical_Data_Sheet.pdf
  20. Google. 2025 Environmental Report (fiscal year 2024), pp. 108–110 and endnote 166: annual PUE 1.16 at Storey County, Nevada, an air-cooled campus, and 1.09 at Henderson, Nevada, an evaporative one; and the fleet's trailing twelve-month PUE, about 1.09, at datacenters.google/efficiency. https://www.gstatic.com/gumdrop/sustainability/google-2025-environmental-report.pdf
  21. Solomon, S. Sustainable by design: Next-generation datacenters consume zero water for cooling. Microsoft Cloud Blog, December 9, 2024. Dropping evaporative cooling brings a "nominal increase" in annual energy use. https://www.microsoft.com/en-us/microsoft-cloud/blog/2024/12/09/sustainable-by-design-next-generation-datacenters-consume-zero-water-for-cooling/
  22. Amazon. How Amazon is making its data centers more water-efficient. June 11, 2026. Chillers use 25% to 35% more electricity than evaporative cooling on the hottest days. https://aboutamazon.com/news/sustainability/amazon-data-center-water-usage
  23. Goel, S., Rosenberg, M., and Eley, C. ANSI/ASHRAE/IES Standard 90.1-2016 Performance Rating Method Reference Manual. Pacific Northwest National Laboratory, PNNL-26917, 2017. Tables 77–83: chiller performance curves, air- and water-cooled. https://www.pnnl.gov/main/publications/external/technical_reports/PNNL-26917.pdf
  24. ASHRAE. Addendum x to ANSI/ASHRAE/IES Standard 90.1-2019. February 4, 2022. Table 6.8.1-3: minimum chiller efficiency, air-cooled COP 2.96 at 35 °C outdoor air, water-cooled centrifugal over 600 tons COP 6.28. https://www.ashrae.org/file%20library/technical%20resources/standards%20and%20guidelines/standards%20addenda/90_1_2019_x_20220204.pdf
  25. Water Ledger design note 0008, Power at the grid: a campus's hourly electricity times the hour's water per kWh at its balancing authority's plants, from EIA-930 hourly generation by fuel and EIA-923 cooling water by plant; average and marginal mix; the balancing authority's own generation, imports not counted. https://github.com/northlinehydrology/waterledger/blob/main/docs/design/0008-power-at-the-grid.md
  26. Reig, P., Luo, T., Christensen, E., and Sinistore, J. Guidance for Calculating Water Use Embedded in Purchased Electricity. World Resources Institute working paper, 2020. Appendix 1: water consumed per kWh by eGRID subregion, counting hydropower reservoirs; 1.31 gal/kWh for AZNM (Arizona and New Mexico). https://files.wri.org/d8/s3fs-public/guidance-calculating-water-use-embedded-purchased-electricity.pdf
  27. Torcellini, P., Long, N., and Judkoff, R. Consumptive Water Use for U.S. Power Production. National Renewable Energy Laboratory, NREL/TP-550-33905, 2003. Tables 2–3: 7.85 gal/kWh for Arizona, counting hydropower reservoirs. https://www.nrel.gov/docs/fy04osti/33905.pdf
  28. Meta. 2025 Environmental Data Index. October 2025. Fleet PUE 1.08 in 2024. https://sustainability.atmeta.com/wp-content/uploads/2025/10/Meta_2025-Environmental-Data-Index.pdf
  29. Uptime Institute. Global Data Center Survey 2025. Keynote Report 180, July 2025. P. 7: average PUE 1.54; 1.44 for sites of 20 MW or more; 1.48 for sites built since about 2020. https://datacenter.uptimeinstitute.com/rs/711-RIA-145/images/2025.Annual.Survey.Report.pdf

Planning-level hydrologic assessment. Not engineering design. Built with the open waterledger Python packages. Northline Hydrology.